TN ITME001 Logging Data from InTouch ME to Historian

Last updated: February 28th, 2025

Description

  • Author: Rich Brooks
  • Published: February 28th, 2025

Details:

Description

This article from InSource shows how to log data from InTouch Machine Edition (ME) to Wonderware Historian. 

  • Author: Rich Brooks 
  • Published: 4/17/2017
  • Applies to: InTouch ME v8.0 and higher

Details

Start by listing the tag(s) that need to be logged to the Historian. Open the trend worksheet by selecting Insert | Trend from the InTouch ME menu.

Configure the Historian connection by click on the Historian Configuration... button.

Enter the Historian server name to replace localhost. The user needs to be a member of the aaAdminstrators group. Leave the default for the gateway host and port. Click on the OK button. Save the trend worksheet when complete.

A connection is made to the Historian using the Database Gateway provided by InTouch ME. Copy the installer from the development workstation to the panel PC. The GatewaySetup installer is located in the following folder:

C:\Program Files (x86)\Wonderware\InTouch Machine Edition v8.0\Redist\DatabaseGateway

Run the GatewaySetup exe file to install the program on the panel PC.

Next startup the Studio Database Gateway, if it is not already running. You will see the icon on the task bar when running.

The Studio Database Gateway application file location is shown above.

Double-click on the Studio Database Gateway from the hidden icons in the lower right of the task bar.

This window allows the user to monitor the logging. Select Log | Options from the menu.

Select All Messages, Message Type, and Date/Time from the dialog. Click the OK button.

Run the InTouch ME project to launch the runtime application.

The data insert status will be displayed. You may also check the SMC on the Historian.

All of the InTouch ME trend tags will be listed under MDAS/Manual Tags.

Verify the data from the trend client. The tags are logging as shown below.

 

logging transfer
Give feedback about this article

Recommended articles

TN - 1240 Creating a Watchlist Using an Import File

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Group Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand