Some content on this site is available only to logged-in subscribers. Contact Us for information on becoming a subscriber.

InSource.Solutions | InSource Training | InSource Client Portal
InSource Solutions Logo
Log In Sign Up
InSource.Solutions InSource Training InSource Client Portal Log In Sign Up
  • Home
  • AVEVA Edge
  • AVEVA Edge Tech Notes

TN - 1504 Using Omron Driver in Aveva Edge

Last updated: September 11th, 2026

Description

  • Author: Rich Brooks
  • Published: September 11th, 2026

Details:

  • Document Version: 
  • Applies to Version(s): AVEVA Edge 2023 R2 or higher 

 

Description:  

This article from InSource shows how to resolve a “Cannot load OMRON. (126)” error popup when opening AVEVA Edge.

 

Solution Steps:

 

The following error popup is seen when an Aveva Edge project is opened without the CX-Compolet installed.

Aveva Edge does require the CX-Compolet to be installed on the runtime machine when the Omron driver is used.  Note: It is not necessary for thin clients (Secure Viewer, Web Thin Client, Mobile Access) because these are only used for visualization.  

The CX-Compolet Ver 1.80 may be downloaded from the Omron website.  It will appear in Programs and Features from Control Panel after it is installed.

Aveva Edge will open the project with no error popup after the CX-Compolet is installed.  The driver sheets will be accessible from the Comm tab.

 

 _____________________________________________________________________________________________________

 

omron aveva
Give feedback about this article

Recommended articles

[ISS Support Case] AVEVA Edge 2020 and Omron 1.24 driver

I have the following installed AVEVA Edge 2020, Omron(1.24)driver, and Compolet 1.8. When I try to assign a tag to I/O address E0_1 Edge will either crash or change E0_1 to E0. I am seeing this issue with Edge 2023 installed on another PC. InduSoft 8.1 works fine. How can I get this to work with 2020 and 2023

Read More

[ISS Support Case] OI ABCIP support for SLC500 Firmware 30

Direct email: I would like to find out what is the latest OI server that will communicate with Studio 5000 firmware 33, SLC500 and compact logic firmware 30. I read from Insource website and found out the OI ABCIP vG2.0 only supports up to Firmware 30. Thanks https://knowledge.insourcess.com/?title=Visualization_and_Supervisory_Control%2FDA_%2F%2F_OI_Servers%2FMaximize_%26_Optimize%2FTN_DAS163_DA_and_OI_Server_Hardware_Compatibility_Guide.

Read More

[ISS Support Case] PLC Communication Failure

Client reached because after user migrated the Galaxy none of the tags are communicating.

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Group Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand