TN - APPSRV - 26072102 Unable to Connect to Galaxy

Last updated: July 21st, 2026

Description

Galaxy Repository Service Issue

  • Author: Josh Andrade
  • Published: July 21st, 2026

Details:

  • Document Version: 001
  • Applies to Version(s): All

 

 

Description  

After performing a reboot on the GR machine, the customer cannot connect to their IDE because the AVEVA Galaxy Repository Service cannot start successfully.

Problem Description:

After rebooting, they attempt to open IDE like normal, but:

There were two SMC warnings that would come in every time they saw this popup:

The software would open, but nothing would ever populate:

They saw their machine name in the drop down, but after attempting to select it and the software hanging for a few minutes, they would get the same “Unable to connect” message and SMC warnings.

 

If you search for these warnings, you’ll find several remote connection related issues. In this case, everything was local. Change Network Account Utility fixed most of the past cases but didn’t fix it here. 

The bootstrap service was running, but GR service would not start:

We ran a PCS scan, everything looked good. No errors:

 

Solution Steps:

For some reason, their temp folder from “C:\Program Files (x86)\ArchestrA\Framework\Bin\Temp” had over 160k files:

 

After deleting these files, and rebooting the machine; the customer was able to start the AVEVA Galaxy Repository service and open IDE.

                                     _____________________________________________________________________________________________________

 

galaxy disconnect
Give feedback about this article

Recommended articles

[ISS Support Case] Unable to Connect to Galaxy

Unable to connect to galaxy after a reboot. SMC throws a message "Unable to impersonate archestra user

Read More

[ISS Support Case] Unable to Create a galaxy

Creating New galaxy in the default galaxy type and it is not allowing him to do so.

Read More

[ISS Support Case] lost connection to PLC

PLC L33er- compact logix is able to ping the PLC

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Group Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand