TN AppSvr323 Backing up and Restoring Objects to a new Galaxy

Last updated: February 28th, 2025

Description

  • Author: Brian Schneider
  • Published: February 28th, 2025

Details:

Description

This article from InSource shows the process for restoring a galaxy from a backup of all objects and importing them into a new galaxy.

  • Author: James Clark
  • Published: 04/08/2019
  • Applies to: Application Server (All Versions)

Details

This article describes one method for backing up and restoring a Wonderware System Platform galaxy by backing up all objects from the existing galaxy and then creating a new galaxy from the backed up data.

This method is not the preferred method as it does not maintain the galaxies security configurations or the application's script functions. This method can be used in the event of a corrupt galaxy and should be used as a final measure.

Step 1

Open your existing galaxy in the IDE. Click Galaxy and select Export | All Objects to backup the objects to be moved to the new galaxy.

Select the save location for the file, and wait for the export to complete.

Step 2

Once the export has completed click close. Close the IDE.

Reopen the IDE and click New Galaxy to create the new galaxy.

Select the appropriate GR node and galaxy type, then name your new galaxy. Click create.

Once the galaxy creation process has completed, click Close.

Step 3

Connect to the new galaxy and go to Galaxy and selct Import | Objects

Locate the .aaPKG file that was created during the export and select it. 

Click open.

Use default settings for importing into a blank galaxy.

Step 4

Once the import is complete click close.

Check your application and verify that all objects imported successfully in your application.

Page tree recommended by the template: Template:Custom/GENERAL_InSource_Template

backup transfer
Give feedback about this article

Recommended articles

TN - 1240 Creating a Watchlist Using an Import File

Read More

TN 1242 Aveva Historian Storage Locations and Best Practices

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Group Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand