TN AppSvr245 How to make sure an individual item within an OPC Client object will always be active

Last updated: March 17th, 2026

Description

  • Author: Brian Schneider
  • Published: March 17th, 2026

Details:

Description

This article from InSource shows how to make sure an individual item within an OPC Client object will always be active.

  • Author: Joseph Hefner
  • Published: 5/18/2017
  • Applies to: Application Server 2014 R2 and later

Details

Step 1)

Within the OPC Client object, click the Scan Group tab and click the "+" button if a scan group does not currently exist:

Step 2)

Type the name of the OPC Device group and select an update interval. After that click the Scan Mode and choose "ActiveAll":

Step 3)

Click the "+" button in the associated attributes section to add a new attribute and give the associated attribute a name. In this example it is called "A1":

Step 4)

Click the Attributes tab and create a new attribute to link to the associated attribute from the OPC device group:

Step 5)

Give the attribute a name and select the I/O button:

Step 6)

Click the Save button and then click the browse button in the I/O section:

Step 7)

Select the relative reference icon on the top and then select the newly added associated attribute and click the "OK" button:

Step 8)

Click the "Save and Close" icon and then check the object in and deploy:

 

opc client activity
Give feedback about this article

Recommended articles

How to receive group emails

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Group Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand