Details:

Description

Platform Partner Status shows as “Unknown”

  • Author: Glenn Yancey
  • Published: 10/30/2015
  • Applies to: System Platform

Details

When deploying platforms with their respective redundant engines, the AppEngine’s “.PartnerStatus” shows as “Unknown” in the Object Viewer inside the ArchestrA IDE. 

In this scenario, the following is true:

Under Control Panel\All Control Panel Items\Windows Firewall, the Firewall has been turned on. Due to our security in this scenario, we are unable to turn off the Firewall.

Resolution:

There are necessary ports that need to be open for communication to exist between redundant engines on different platforms. This is only necessary if we have firewalls that are forced on.

TCP Ports:

30000

30001

32568

In the Firewall, we would create 3 “Inbound Rules” for these ports by selecting Advanced Settings in the Windows Firewall.

A redeploy might be necessary to test this. However, “.PartnerStatus” should now hopefully come back with a value of “Standby” with good quality, rather than “Unknown”. 

The example below shows the Object Viewer with the PartnerStatus attribute shown, rather than results of the Inbound Port changes.

 

unrecognized partnership
Give feedback about this article

Recommended articles

TN 1398 Determining Active Communications Server

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Group Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand