TN Appsvr136 Alarm Shelving

Last updated: February 28th, 2025

Description

  • Author: Brian Schneider
  • Published: February 28th, 2025

Details:

Description

About alarm shelving in Wonderware System Platform version 2014 R2

  • Author: Peter Farrell
  • Published: 6/25/2015
  • Applies to: System Platform 2014 R2

Details

You can shelve alarms to temporarily hide them from displays for a fixed period. Alarms continue to be historized, even when they are shelved.

Shelving typically is used to reduce alarm “noise”, or to temporarily suppress alarms that might be triggered during system modifications or repairs, allowing you to focus on correcting other more urgent alarms.

Shelving is similar to silencing an alarm, but shelved alarms differ from silenced alarms in the following ways:

Shelved alarms have a built-in associated timeout. Shelved alarms are automatically unshelved when the configured shelving period expires. You can also manually unshelve alarms and return them
to an active, displayed state.

Alarm shelving must be enabled at an area level, but shelving applies only to individual alarms. You cannot shelve a hierarchy of alarms for for an entire area or for an entire object. You cannot propagate alarm shelving through the Model View hierarchy.

The system enforces role-based limitations on permission to shelve alarms, alarm severity levels that can be shelved, and the total number of alarms a user can shelve.

The system tracks who shelved the alarm, from what workstation, the reason for shelving the alarm, when shelving began, and when shelving will expire. Shelved alarms aggregate in similar fashion to silenced alarms.

A set of seven attributes provide run-time alarm shelving information and control:

AlarmShelveCmd

User writeable. Use this attribute to shelve or unshelve an alarm.

Default values: Duration = 0,

Reason = “”

AlarmShelved

Read-only, Boolean value. Shows True if alarm is shelved, False if alarm is unshelved.

Default value: False

AlarmShelveStartTime

A read-only date/time stamp indicating when alarm shelving began, based on the engine time when the shelving request was received,

Default value: Blank

AlarmShelveStopTime

A read-only date/time stamp equal to the AlarmShelveStartTime plus the duration for which the alarm is
to be shelved.

Default value: Blank

AlarmShelveReason

A read-only string value providing the reason for which the alarm was shelved or unshelved by the Alarm Shelve command.

Default value: Blank

AlarmShelveUser

Read-only, the name of the user who most recently shelved or unshelved the alarm with the Alarm Shelve command.

Default value: Blank

AlarmShelveNode

Read-only, the name of the computer node from which the user most recently shelved or un-shelved the alarm with the Alarm Shelve command. If the node is hosted in a Terminal Server client session,
the node and the TSE ID are both identified.

Default value: Blank

shelving alarm
Give feedback about this article

Recommended articles

TN - 1240 Creating a Watchlist Using an Import File

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Logo

© 2025 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand