TN Appsvr117 Importing Windows Forms Client Controls into ArchestrA Graphics

Last updated: March 19th, 2025

Description

  • Author: Brian Schneider
  • Published: March 19th, 2025

Details:

Description

This document provides step by step instructions on importing the Windows Forms client controls into Application Server. The Microsoft System.Windows.Forms.dll provides fifty plus client controls that may be utilized in ArchestrA graphics. Installation is a simple process of importing the .dll file, and then graphically adding the desired control from the Symbol Editor. Controls such as the Web Browser, Progress Bar, Month Calendar, and more are easily embedded using the graphical development environment.

Overview

This document provides step by step instructions on importing the Windows Forms client controls into Application Server. The Microsoft System.Windows.Forms.dll provides fifty plus client controls that may be utilized in ArchestrA graphics. Installation is a simple process of importing the .dll file, and then graphically adding the desired control from the Symbol Editor. Controls such as the Web Browser, Progress Bar, Month Calendar, and more are easily embedded using the graphical development environment.

Pre-requisites

Install Wonderware Application version 3.5 or higher. Refer to the installation guide as supplied with the System Platform 2012 or higher DVD. Create a galaxy with the template of your choice. Connect to the galaxy repository to open the Integrated Development Environment (IDE).

Import client control

The first step in the configuration is to import the client controls from the .dll file. 

Select Galaxy – Import – Client Control… from the ArchestrA IDE menu as pictured below.

Browse to the following folder from the Windows Server 2008 operating system:

C:\Windows\Microsoft.NET\Framework\v2.0.50727\

Highlight the System.Windows.Forms.dll file and click on the Open button. 

Click the OK button to accept the default Skip: Do not import to avoid the import of controls with the same Tagname as an existing object.

The import of the client controls will proceed. Wait for the Import completed notification before clicking the Close button.

The Windows Forms Client Controls are now installed and ready for use.

View the IDE Graphic Toolbox to see the various Windows Forms Controls.

Using the Client Controls

Create a new symbol or open an existing symbol to add one or more of the client controls.

Right click on the Graphic Toolbox – Galaxy to select New – Symbol.

Right click on the new symbol or double click to open the new symbol for editing.

The Symbol Editor will be launched. Click on the Client Control tool to open the Galaxy Browser.

Select the Web Browser control from the available controls.

Drop the control on the Symbol Editor by clicking on the drawing pane. Resize the control as desired.

Double click the control to open the properties pane. Add a URL Reference to a custom property.

archestra graphics windows forms
Give feedback about this article

Recommended articles

TN - 1240 Creating a Watchlist Using an Import File

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Group Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand