TN - AppSvr - 26061109 Template Toolbox is Empty

Last updated: June 11th, 2026

Description

  • Author: Sam Soens
  • Published: June 11th, 2026

Details:

  • Document Version: 001
  • Applies to Version(s): Application Server 2023 R2 SP1

 

 

Description  

In the ArchestrA IDE, your Template Toolbox can become empty. There is no arrow to expand the tree and it appears that all the templates are gone. The cause of this is unknown. You could have just been in the ArchestrA IDE an hour ago and working just fine, then you came back and Template Toolbox was empty.

Solution Steps:

Close the ArchestrA IDE.

In SQL Server Management Studio, run the following script in your Galaxy Repository:

update folder set depth = 1 where parent_folder_id = 0

Open the ArchestrA IDE.

                                     _____________________________________________________________________________________________________

 

empty templates template toolbox
Give feedback about this article

Recommended articles

[ISS Support Case] Deployment not working

System is running slow. Original issue is the orange icon is slow Undeploy/redeployed and still taking a long time. Getting some request timeouts but deployments still seem to go through? Sent old school platform remover and will do this on one of the clients and will redeploy each object back out again.

Read More

[ISS Support Case] Platform Deployment Failure

Client reached out as when user was attempting to deploy WinPlatform user was receiving the following error: "Cannot find the target PC on the network OR target PC can not communicate back to the Galaxy Repository using the NIC that is top in the binding order."

Read More

[ISS Support Case] Platform deployment failure

Failed to deploy failed to find target platform aa bootstrap register platform failed.

Read More

TN AppSvr255 Using the correct AlarmClient (2014 R2 or later) to connect to History Block alarms.

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Group Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand