Details:

Description

This article from InSource shows how to resolve a problem with platform deployment for AVEVA Application Server. The deployment fails to deploy with an Access Denied WWCdi error message. A deployment failure message related to the login and/or password may also be seen.

  • Author: Rich Brooks
  • Published: 8/17/2022
  • Applies to: Application Server 2020 R2 SP1 and higher

Details

The platforms failed to deploy for Windows 10 workstations only. An access denied message was found in the SMC Log Viewer.

Login and/or Password Mismatch error messages were sometimes seen during deployment instead of the Access Denied message.

A DCOM error was found in the event viewer at the time of the platform deployment.

Searching on RPC_C_AUTHN_LEVEL_PKT_INTEGRITY found the Microsoft Update KB5004442 - DCOM Hardening.

The DCOM Hardening key was disabled in the registry to resolve this issue.

HKEY_LOCAL_MACHINE\SOFTWARE\Microsoft\Ole\AppCompat

Value Name: "RequireIntegrityActivationAuthenticationLevel"

Type: dword

Value Data: default = 0x00000000 means disabled. 0x00000001 means enabled. If this value is not defined, it will default to enabled.

Restart the device after setting this registry key for it to take effect.

permission error deployment issue
Give feedback about this article

Recommended articles

TN 1398 Determining Active Communications Server

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Group Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand