TN 1206 Understanding and resolving logger informational messages showing repetitions of “Partially Connected” and “Connected”

Last updated: March 6th, 2025

Description

  • Author: Brian Schneider
  • Published: March 6th, 2025

Details:

Description

This article from InSource shows...

  • Author: Peter Farrell
  • Published: 12/16/2021
  • Applies to: Application Server all versions

Details

If, in a redundant IO environment, the System Management Console is filling with informational level messages which show a redundant topic partially connected and then connected, you may need to consider changing the configuration and/or architecture.

The logger messages may look similar to the following.

 

Status of Backup DI source [MyRedundantIOSource] is Partially Connected

Status of Backup DI source [MyRedundantIOSource] is Connected

There are a couple of reasons that you may see the repeating informational messages advising of a partial connection and then connection.

  1. You may have more then one PLC (topic/device group) included within a single redundant IO object. The problem with such an architecture is that if one of your PLCs is down, the object will then show a partially connected status.
  2. You may not have defined a ping item for your topic/device group. Under this circumstance, the system will choose a ping item which may itself not be a good choice and become unavailable. You should always specify a ping item.

Shown below in the screen shot is a configuration of a redundant DI Object which includes more than one PLC and no ping items defined for the scan groups.

If possible, each Redundant DI Object should contain only a single PLC/Device/Scan Group and you should identify a PLC IO item which can be used for each device group/scan group defined for that PLC.

In the example shown below, the configuration/architecture has been changed such that the object hosts only a single PLC and each scan group has been configured for a ping item, which is a PLC item reference. Failure to add a ping item can result in unnecessary failover conditions.

 

logger messages connection issues
Give feedback about this article

Recommended articles

How to receive group emails

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Logo

© 2025 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand