TN AppSvr165 Understanding Application Server IO Scan Modes

Last updated: March 9th, 2025

Description

  • Author: Michael Viteri
  • Published: March 9th, 2025

Details:

Description

This guide from InSource will help you understand the scan modes in application server when talking to IO. The options are:

Active

ActiveAll

ActiveonDemand

  • Author: Mike Viteri
  • Published: 11/9/2015
  • Applies to: Application Server

Details

The differences between the scan modes are listed below

Active

  • Items are deleted and added to the scan group as requested (referenced) by the clients. 
  • Items that exist when a scan mode change occurs are not deleted unless the previous mode was ActiveAll and the items are no longer referenced.
  • The Active scan mode polls all points that are referenced, whether active or inactive. 
  • In Active scan mode an attribute is always in the active state. When the last reference to the attribute is unregistered/unadvised, the attribute is deleted. 

ActiveAll

  • Scanning is continuous and dynamic attributes are never removed when unsubscribed.
  • Items are activated by client requests, but continue to exist even after the client are not interested in them anymore.
  • Items are not removed when the scan mode changes.
  • The scan group polls the field device for all points irrespective of whether they are currently active, inactive, or even subscribed to by items.

ActiveOnDemand

  • When the scan mode is configured as ActiveOnDemand, attributes that are not actively being referenced by any client or object are made Inactive and are not scanned.
  • New Items are deleted and added to the scan group as requested (referenced) by clients.
  • Items that exist when a scan mode change occurs are not deleted unless the previous mode was ActiveAll and the items are no longer referenced.
  • ActiveOnDemand scan mode polls the field device for currently active items only. Inactive items are not scanned. 

 

io scan server modes
Give feedback about this article

Recommended articles

TN 1242 Aveva Historian Storage Locations and Best Practices

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Group Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand