TN Appsvr135 How to Shelve an Alarm in Object Viewer

insource logo large.jpg

 

One of the new additional features is the ability to shelve and unshelve alarms in RunTime. This document will walk you through the process of doing this. 

 

 

  • Author: Davenport Alex
  • Published: 06/25/2015
  • Applies to: AppServer 2014 R2

 

 

 

1 Open Object Viewer and browse to the Object in question you wish to shelve alarms on. Select the attriubute you wish to shelve and add this into the Watch Window.

 

Shelve1.JPG

 

2 Once the attribute has been added to the Watch Window and we can see a Good value then double click the attribute.

 

 

Shelve2.JPG

 

Shelve3.JPG

 

3 The below Dialog screen appears.

 

Shelve4.JPG

 

4 Enter a duration in hours you wish the alarm to be shelved for and if it's less than an hour you will need to use decimal fractions. Then enter a Reason (you must enter something) then click the apply button. The alarm will be shelved

 

Shelve5.JPG