TN Appsvr118 Resolving a failure to open Galaxy when no network is connected

Overview

If a laptop on which a GR with a deployed Galaxy is shut down and removed from the network, attempts to connect to the Galaxy on restart WITHOUT a network connection may fail with a Windows popup titled "ArchestrA IDE" which states, “ArchestrA IDE has stopped working.  A problem caused the program to stop working correctly. Windows will close the program and notify you if a solution is available.”

 

Loopback_000.png

Resolution

It is possible to resolve this situation and connect to the Galaxy without issue by installing the Microsoft legacy loopback network adapter using the following procedure:

 

Click the Start menu.

Search for “cmd".

Right-click on “cmd” and select “Run as Administrator”

Enter “hdwwiz.exe”

 

Loopback_001.png

 

In the "Welcome to the Add Hardware Wizard", click Next.

 

Select "Install the hardware that I manually select from a list (Advanced)" and click Next.

 

Loopback_002.png

 

Scroll down and select "Network adapters" and click Next.

 

Loopback_003.png

 

Select under Manufacturer "Microsoft" and then under Network Adapter "Microsoft Loopback Adapter" and click Next.

 

Loopback_004.png

 

IMPORTANT - The machine should be rebooted, after which it should be possible to successfully connect to the Galaxy with no network connection established.