TN AppSvr161 Unspecified Error 80004005....CreateGalaxy.cpp

insource logo large.jpg

 

Description

Resolving the following error when creating a Galaxy: "Error  - Unspecified error (80004005) caught at line 856 in CreateGalaxy.cpp".

 

  • Author: Glenn Yancey   
  • Published: 10/30/2015
  • Applies to: System Platform

 

 

Details

Error  - Unspecified error (80004005) caught at line 856 in CreateGalaxy.cpp

 

When creating a Galaxy, an error occurs that says “Unspecified error (80004005) caught at line 856 in CreateGalaxy.cpp”.

 

File:C:/Users/gyancey/AppData/Local/Temp/msohtmlclip1/01/clip_image002.jpg

This error specifies that the current aaAdminUser does not have the credentials to create a galaxy. 

 

Resolution

To resolve this error, you must run the Change Network Account by going to:

Start->All Programs->Wonderware->Common->Change Network Account

File:C:/Users/gyancey/AppData/Local/Temp/msohtmlclip1/01/clip_image004.jpg

Supply the computer name, a user name, and password.   If a user doesn’t exist on this machine, you will need to create a user.   This will require a reboot.