Installing and configuring the ABTCP DA Server

                   

installation.jpg

 
INSTALLATION GUIDE

Description

This Tech Note was written as a general walkthrough for installing and configuring the DASABTCP DA Server 3.0. The actual screens encountered may vary depending on other Wonderware software that is currently installed on the machine.

 

Author

Benjamin Davis

Publish Date 01/15/2014

Applies to Software

DASABTCP DA Server

Applies to Version

3.0

Applies to System/Module

 

Article Version

01.01.01

************************************************************************************************************************************************************

Pre-Requisites

Edit section

The ABTCP DAServer 3.0 SP1 supports the following Operating Systems:

  • Microsoft Windows XP Pro SP3 (32-bit version)
  • Microsoft Windows 2003 Server SP2 (Standard and Enterprise) (32-bit version)
  • Microsoft Windows 2003 Server R2 SP2 (Standard and Enterprise) (32-bit version)
  • Microsoft Windows Vista SP2 (32-bit and 64-bit) (Ultimate, Business, Enterprise)(see Windows Operating System Restrictions)
  • Microsoft Windows 2008 SP2 (32-bit and 64-bit) (Standard and Enterprise)
  • Microsoft Windows 2008 Server R2 SP1 (64-bit) (Standard and Enterprise)
  • Microsoft Windows 7 SP1 (32-bit and 64-bit) (Professional and Ultimate)
  • Microsoft Windows 7 Embedded (32-bit)
  • Microsoft Windows 8 (32-bit and 64-bit) (Professional and Enterprise)
  • Microsoft Windows 2012 Standard (64-bit)

Detailed Steps

Installation

Launch the setup.exe that is located on the root of the DASABTCP DA Server installation folder.

Once the setup has been launched you should see the screen below. Click the next button to proceed with the installation.

1Install.png

 

 

Next accept the license agreement and then click the Next button.

2Install.png


 

The DA Server installation will shut down any DA Servers that are currently running during the installation. The next screen is an acknowledgment of this fact and a warning that the installation may require a reboot. Press the Next button to proceed.

3Install.png

 

 

Choose the location where you would like to install the DA Server and then click the Next button and then Next at the following screen to proceed. The default location for a 64 bit Operating System will be the location in the screenshot below:

4Install.png

 

 


 

Click Next.

5Install.png


 

Click the Finish button to complete the installation of the DA Server.

6Install.png

 

Configuration

 

Using an existing configuration file

 

The DA Server configuration (.aacfg) files are stored in the specific location depending on the version of the DA Server that is installed. The following locations are for the associated Operating Systems below:

Windows XP \ Server 2003

New Version

C:\Documents and Settings\All Users\Application Data\Wonderware\DAServer\DASABTCP

Older Version(s)

C:\Program Files\Wonderware\DAServer\DASABTCP\Bin

 

Windows 7 \ Server 2008

New Version

C:\ProgramData\Wonderware\DAServer\DASABTCP

 

Older Version(s)

C:\Users\All Users\Wonderware\DAServer\DASABTCP

 


 

If you already have an existing system with the same configuration you wish to use, simply copy the DASABTCP.aacfg file from the working machine to the equivalent location on the new machine. If your new configuration is named something other than DASABTCP.aacfg you will need to switch to the new configuration by right clicking the configuration under the DASABTCP and then choosing “Use Another Configuration Set” and selecting the appropriate configuration file. If the DA Server is activated it will need to be de-activated before you can switch to another configuration.

1Config.png

 


 

Creating a new configuration

 

The first step for creating a new configuration will be to right click on the configuration and choose “Add Port_TCPIP Object.”

2Config.png

 

 

 

 


 

Right click the newly added port. Choose the type of processor you wish to add.

3Config.png


 

In the Host Name field, enter the IP address of the PLC.

4Config.png

 

The next step will be to create topics. To do this you will click on the Device Groups tab within the PLC object.  Next right click and choose Add and create a topic name.

5Config.png

 


 

Save the configuration by clicking the floppy disk in the upper right corner.

6Config.png


 

Right click on the DASABTCP DA Server and choose Activate Server.

7Config.png