Wonderware Antivirus Exclusions
TECHNOTE
Description
Antivirus Exclusions Paths
Author |
Mike Viteri |
Publish Date | 6/28/2013 |
Applies to Software |
All |
Applies to Version |
All |
Applies to System/Module |
|
Article Version |
1.00.01 |
Problem Statement
Wonderware files need to be excluded from Antivirus. What paths should be added to Antivirus exclusions.
Solution Details
Ensure that subfolders of the listed directories are also excluded.
If you are using a 64-bit operating system, folder names must be specified accordingly. For example, the program files root directory in a 64-bit operating system is C:\Program Files (x86)\... and the application data root directory in a 64-bit operating system is C:\ProgramData\...
Antivirus software should not scan files in the following ArchestrA folders in a 32-bit system:
- C:\Program Files\ArchestrA\*.*
- C:\Program Files\Common files\ArchestrA\*.*
- C:\Program Files\FactorySuite\*.* (The FactorySuite directory may not exist in newer installations)
- C:\Program Files\Wonderware\*.*
- C:\InSQL\Data\*.*
- C:\Historian\Data\*.*
- C:\Documents and Settings\All Users\Application Data\ArchestrA*.*
Antivirus software should not scan files in the following ArchestrA folders in a 64-bit system:
- C:\Program Files (x86)\ArchestrA\
- C:\Program Files (x86)\Common files\ArchestrA\
- C:\Program Files (x86)\FactorySuite\ (The FactorySuite directory may not exist in newer installations)
- C:\Program Files (x86)\Wonderware\
From Wonderware Application Server Platform objects:
- History Store Forward directory default location:
- C:\Documents and Settings\All Users\Application Data\ArchestrA\
- C:\Users\All Users\ArchestrA\
- Checkpoint directory location default location:
- C:\Program Files\ArchestrA\Framework\bin
- C:\Program Files (x86)\ArchestrA\Framework\bin
- InTouch HMI Application folder path:
- C:\Documents and Settings\All Users\Application Data\ArchestrA\
- SMC Logger Storage file path:
- C:\Documents and Settings\All Users\Application Data\ArchestrA\LogFiles\
- SQL Server database files of type:
- .mdf
- .ldf
Wonderware Information Server
Antivirus Software Exclusions
After installing Wonderware Information Server, configure your antivirus software to prevent files in the following folders from being scanned:
- \inetpub\wwwroot\Wonderware
- \\inetpub\wwwroot\AFWeb
- \\inetpub\wwwroot\aaFlexLicWebService
- \\Program Files\Wonderware\SuiteVoyager
Note: Ensure the subfolders of the listed directories are also excluded. Specify folder names accordingly if you are using a 64-bit operating system. For example, the program file's root directory in a 64-bit operating system is C:\Program Files (x86)\... and the application data root directory in a 32-bit operating system is C:\ProgramData