047297 - Errors during object deployment - "Login Failure.." and others

Problem

When trying to deploy, get the following errors: LogonUser failed. Error 1385 (0x00000569): Logon failure: the user has not been granted the requested logon type at this computer Cannot enumerate folders in "______________" FindFirstFile failed. Error 5 (0x00000005): Access is denied CGlobalDataDistributionClient::Execute CallGlobalDataCacheMonitor return 0x80004005 will retry. Execute - spGlobalDataDistributionClient -> Execute FAILED ERROR CODE 80004005

Product Version: 3.1

ProdSp: SP3

OS: Win 2008 32 bit

Solution

User had seen that rerunning the Change Network Account utility would fix the issue temporarily, but then the issue would begin to come up again. The user found that their corporate IT had been modifying the permissions on the Wonderware Network User account, and this is why the system was unstable. He is working with corporate to get this resolved.

Close Date: 2013-04-18 08:43:24