66127 - Looking for migration steps for Wonderware Intouch

Problem

Looking for migration steps for Wonderware Intouch v10.1.300 on Win XP to Win8.1 for Wonderware Intouch 2014 R2.

Product Version: 11.1

Solution

These are steps you need to take if this is a standalone application � Please make sure you have a backup of the Application folder before you start this process. 1 Install the InTouch software you need on the new Windows 8.1 machine. 2 Once installed use InTouch Application Manager to search for your Application Folder and then open this in WindowMaker 3 It will ask you if you wish to upgrade and select yes but DO NOT select yes to incorporate ArchestrA graphics 4 InTouch will automatically upgrade the application for you. 5. Make the necessary changes to scripts and load the relevant ActiveX's Customer has only Runtime licenses so will either have to engage our Services Team or purchase the necessary license.

Close Date: 11/7/2016 15:48