Skip to main content
InSource KnowledgeCenter

042824 - Historian Client gives 15 minute demo - cannot find license

Problem

Customer has a number of machines which use a concurrent Historian Client License. He tried setting up a new machine, and Historian Client does run, but it goes into 15 minute demo mode.

Product Version: 10.0

OS: Win 2003

OS_SP: SP2

Solution

Customer had not gone into the License Manager and added the license server entry. To do this, go to the License Manager (Start > Programs > Wonderware > Common) and from the File menu select "Add License Server". This will allow you to specify the computer which has the server license installed. This way ActiveFactory/HistorianClient will look for the licenses on that computer, instead of on the local system.

Close Date: 2012-02-14 13:19:43