TN IT250 Connecting to an InTouch application from the Wonderware Gateway OI Server

InSource_Logo_Transparent.png

Description

 

This article from InSource walks through the process for connecting to an InTouch application from within the Wonderware Gateway OI Server.

  • Author: Joseph Hefner
  • Published: 12/6/2016
  • Applies to: Gateway OI Server 1.0 or later

Details

 

Step 1) Right click the configuration and choose "Add InTouch Connection":

Capture.jpeg

 

Step 2) Enter a value for the fields below.  The Device Group Name will act as the topic name when trying to connect to the application at a later time. After entering the information and selecting the application click the "Tag Browser" button to select the tags you wish to make available over the Gateway server.

Capture2.jpeg

Step 3) Select the tags you wish to make available and click the "OK" button.

Capture3.jpeg

Step 4) Click the Device Items tag to ensure the tags were added.

Capture4.jpeg

Step 5) Right click on the Gateway OI Server and select "Activate":

​​​​​​Capture5.jpeg

 

Step 6) Test the connection.  This can be done using the Wonderware Client as below. First create the connection:

Capture6.jpeg

Next enter the Gateway instance name as your application and Device Group Name from step 2 above:

​​​​​​Capture7.jpeg

Finally, enter the tagname as your Item and click the "AdviseEx" button:

Capture8.jpeg

If the tag has good quality you should see a value of 0x00c0 for the last value in the client.

Capture9.jpeg