Skip to main content
InSource Solutions

TN Appsvr224 Platform deploy failed with Failed to create RMC error in the SMC

InSource_Logo_Transparent.png

When trying to deploy you will see the error message Platform deploy failed with Error Failed to create RMC in the SMC

 

This article from InSource shows...

  • Author: Alex Davenport    
  • Published: 02/07/2017
  • Applies to: Application Server All versions

When trying to deploy you will see the error message Platform deploy failed with Error Failed to create RMC in the SMC

1. Logon with the Archestra Admin Account or equivalent to the Server  
2. Open the CMD Window  
3. Browse to C:\Program Files (x86)\ArchestrA\Framework\FileRepository\Playground\Vendors\ArchestrA and locate the MessageChannel.dll  
4. Enter in the cmd window following command: REGSVR32 followed by a space 
5. Drag and Drop the MessageChannel.dll into the cmd Window
6 Once completed then deploy the Platform