TN - 1040 No Alarms in Window Viewer

After migrating an application, Window Viewer no longer displays alarms in the alarm client or the alarm summary.

No Alarms in Window Viewer

Description:

After migrating an application Window Viewer no longer displays alarms in the alarm client or the alarm summary.

Confirm the following configuration:

 Inside your DDESuitLinkClient Object ensure you have “Detect connection Alarm” Checked!

Enter your desired alarm comment without using “me.desc” 

1.jpg

2.jpg

 

What if this doesn’t work?

“Often times, InTouch may startup prior to the bootstrap causing window viewer no to reflect the updated information. This may be due to a startup script; however, the following steps will correct the issue for now.  “

 Verify the Alarm Query is correct. (?)

4.jpg

 

 Verify the client is being referenced correctly. (?)

5.jpg 

Below you will see no alarms are displayed on either screen.

6.png

*      Next we will navigate to the home screen of your PC/Device

*      Right click your taskbar 

*      Select task manager

*      Navigate to processes 

7.jpg 

*      End all running “alarmmgr.exe”

8.jpg\

*      Navigate to services on your PC 

 

9.jpg 

*     Select ArchestrA Bootstrap

10.jpg

11.PNG

 

 

*      Restart

12.PNG 

*      Open Window Viewer

13.PNG

 

 The alarms will now be displayed

14.PNG