Historian Trends shows Nulls and Historian logger says "buffer overflow."

problem-solving.jpg
SOLVER

                 

Description

Historian Trends shows Nulls and Historian logger says "buffer overflow."

 

Author

Mike Viteri

Publish Date 9/9/2014

Applies to Software

Historian

Applies to Version

10.x

Applies to System/Module

 

Article Version

00.00.01

************************************************************************************************************************************************************

 

Detailed Steps

 

When using Historian Software 10.x or later you will see a message below in the smc log viewer.

 

Server is too busy.


Buffer overflow.
 

Edit section

historian.JPG

 

This error will cause data graps in your trend. The most likely reason you are seeing this issue is that a time sync is running and changing the historian clock time. This is especially true if you are running your Historian on Hyper-V or VMware. The way to fix this error is to not change the Historian time. Have all you clients sync their time to the Historian using net time. The attach technote explains how to setup net time.