Skip to main content
InSource Solutions

TN Hist242 Setup for Redundant Historians

insource logo large.jpg

 

Description

This technote from InSource describes the setup required for redundant Wonderware Historians.

 

  • Author: Rich Brooks
  • Published: 11/6/2015
  • Applies to: Historian v11.6 and higher

 

 

Details

Redundancy is enabled from the System Management Console (SMC) on each of the Historians.  Open the SMC from one of the Historian to expand out the Configuraton Editor - System Configuration - Parameters.

Pic1.png

Highlight and right-click on the HistorianPartner parameter to open the properties dialog.

 

Pic2.png

Type in the machine name of the partner Historian and click OK to save and close.

 

Pic3.png

You will be prompted to ensure that the paired Historian is configured as well.  Click the Yes button to close the dialog.

 

Right-click on the configuration editor tree in the SMC to select Commit Pending Changes...  

Pic4.png

Click on the Commit button from the confirmation dialog.

 

Repeat the previous steps from the paired Historian.   Remember to commit the changes.

 

Pic5.png

The redundancy may be verified by reviewing the MDAS tag list from each Historian.  All of the tags pushed from the galaxy should match.  The tags are being stored on both Historians now.